Standardization of input and output data of SCADA/EMS topology processor according to the common information model (CIM).
https://doi.org/10.37493/2307-907X.2025.6.1
Abstract
Introduction. The topology processor is one of the main components of the SCADA/EMS operating core. The evolution of SCADA/EMS requires data standardization for information exchange between the topology processor and application tasks, as the functions of the topology processor are defined by the requirements of industry regulatory and technical documents. Goal. The outlines for the CIM standardization of the topology processor input and output data that ensure interoperability of software components. Materials and methods. This study is based on an analysis of the functional architecture of SCADA/EMS, standards in the field of electric power grid management, and the Common Information Model (CIM) methodology. Results and discussion. Topology analysis tasks are considered: models offline building, model updating after switching operations, switching state recognition, topological interlocks, topological tracing, and post-failure power supply restoration. CIM classes are proposed for input and output data exchange between topology processor and applied components. It is shown that CIM provides a necessary "bridge" between the power engineering language and mathematics (graph theory). Conclusion. CIM standardization of input and output data for the topology processor allows the latter to be developed separately from application modules and delivered ready-to-use for the variety of control systems. This approach can be spread on the other SCADA/EMS software components to ensure their seamless imbedding into integrated control systems.
About the Authors
I. A. GolovinskyРоссия
Ilya A. Golovinskii – Dr. Sci. (Techn.), Chief Specialist in Mathematical Modeling in the Electric Power Industry, Department of Automated Electric Power Systems and Power Supply, Faculty of Oil and Gas Engineering
I. I. Nadtoka
Россия
Ivan I. Nadtoka – Dr. Sci. (Techn.), Professor
S. S. Kostyukova
Россия
Svetlana S. Kostyukova – Assistant at the Department of Automated Electric Power Systems and Power Supply, Faculty of Oil and Gas Engineering; Senior Researcher of the same department.
References
1. STO 56947007-25.040.05.267-2019. Standard Technical Requirements for the ASU PC Software Package of the Grid Control Center for Organizing Remote Control Functions of Substations from Control Centers. FGC UES PJSC, 2019. 159 p. (In Russ.).
2. Golovinskii I. Object-topological modeling of electrical networks. Newsletter of North-Caucasus Federal University. 2024;(6):16-26. (In Russ.).
3. ASU TP KOTMI. A new generation of SCADA, DMS and OMS. Available from: https://kotmi.ru/platforma-kotmi/ [Accessed 20 October 2025]. (In Russ.).
4. STO 59012820.27.010.001-2022. JSC "SO UES". Rules for Displaying Process Information. 188 p. (In Russ.).
5. IEC 61970-301. Energy management system application program interface (EMS-API) – Part 301: Common information model (CIM) base. Ed. 7.0, 2020. – 558 p.
6. GOST R 58651.3-2020. National Standard of the Russian Federation. Unified Energy System and Isolated Power Systems. Information Model of the Electric Power Industry. Profile of the Information Model for Power Transmission Lines and Grid Equipment with Voltage of 110-750 kV. Moscow: Standartinform; 2020. 46 p. (In Russ.).
7. IEC 61970-456. Energy management system application program interface (EMS-API) – Part 456: Solved power system state profiles. (In Russ.).
8. Topological blocking of operational switches / I. A. Golovinsky, M. Y. Dyachenko, M. I. Londer, A.V. Tumakov // Electric stations. 2018. No. 7. pp. 29-37.
9. Golovinskii I. Automation of topological tracing of circuits in electrical network and substation diagrams. Relay protection and automation. 2024;(3):20-29. (In Russ.).
10. Golovinskii I. Possibilities of automatic recovery of power supply in distribution network in case of multiple simultaneous faults. Newsletter of North-Caucasus Federal University. 2021;(4):7-16. (In Russ.).